                                          Useful Information - General Data
Click here for a PDF of page 453
IP Reference Chart No liability can be accepted for the data below which is given for guidance only
In the latest standards SFS - EN 60529 4 1992 concerning the IP degrees of enclosure protection of electrical equipment there are some changes particularly with regard to the testing and identification of protection against liquids. Up to the degree 6 the protection is understood to also cover the lower protection degrees. In degrees higher than 6, each degree is to be tested separately and marked accordingly, e.g. IP67 / IP66
Room containing bath / shower
Areas of the bathroom are split into zones. As a guide only, the requirements for luminaires in each zone may be summarised as follows. Particular care should be taken with wash basins - guidance for these is also contained within BS 7671.
  First number Protection against solid objects
 Second number Protection against liquids
  Third number Protection against mechanical impact
  IP Ø
TEST
No Protection
  IP TEST
 Ø
No Protection
 IP Ø
        TEST
No Protection
   1
2
3
4
5
6
50
12.5
Protected against solid objects up to 50mm e.g. accidental touch by hands.
Protected against solid objects up to 12.5mm e.g. fingers.
Protected against solid objects over 2.5mm e.g. tools, small wires.
Protected against solid objects over 1mm e.g. tools, small wires.
Protected against dust-limited ingress permitted (no harmful deposit).
Totally protected against dust.
           1
2
15˚
3
30˚
Protected against vertical drops of water.
Protected against direct sprays of water up to 15˚ from the vertical.
Protected against direct sprays of water up to 60˚ from the vertical.
Protected against water sprayed from all directions - limited ingress permitted.
Protected against low pressure jets of water from all directions - limited ingress permitted.
Protected against strong jets of water e.g. for use on ship decks - limited ingress permitted.
Protected against the affects of immersion between 15cm and 1m.
Protected against long periods of immersion under pressure.
   4 5
6
   71m 1m
8
150mm
    1
   150g @ 15cm
Impact 0.225 joule
 2
     250g @ 15cm
Impact 0.375 joule
 3
       250g @ 20cm
Impact 0.50 joule
   5
   500g @ 40cm
Impact 2.00 joule
 6
     1.5kg @ 40cm
Impact 6.00 joule
 7
       5kg @ 40cm
Impact 20.00 joule
           Protection
   IP Rating
     Zone 0
  SELV < 12V rms a.c. Transformer must be outside zones 0-2
  IPX7
    Zone 1
 SELV < 12V rms a.c. Transformer must be outside zones 0-2
 IPX4, or if water jets are likely to be used for cleaning purposes in communal baths or showers, IPX5
 Zone 2
   As Zone 1
   As Zone 1
    Zone 3
  No limitation on fixed equipment
  IPX5 if likely to be subject to water jets or cleaning
   Location with bath tub
Zone 2
Zone 3
Outside Zone
Location with shower
  Zone 2
Zone 3
Outside Zone
          ZZone11
Zone 2
0.6m
3m
Zone 3
2.4m
2.25m
Zone 1 Zone 1
          Zone 0
Zone 0
Zone 2
0.6m
3m
Zone 3
2.4m
2.25m